Schneider Electric / Invensys / Foxboro I/A Series Electronic Pressure Transmitters Model IDP10-T with HART Communication Protocol for Differential Pressure Measurement
  • invensys_foxboro_idp10_t22c21f_m1l1_view1_2014115135257
  • invensys_foxboro_idp10_t22c21f_m1l1_view2_2014115135257
  • invensys_foxboro_idp10_t22c21f_m1l1_view3_2014115135257
  • invensys_foxboro_idp10_t22c21f_m1l1_view4_2014115135257
  • invensys_foxboro_idp10_t22c21f_m1l1_view5_2014115135257

Schneider Electric / Invensys / Foxboro I/A Series Electronic Pressure Transmitters Model IDP10-T with HART Communication Protocol for Differential Pressure Measurement

Features

  • Traditional or Low Profile Structures
  • Durable Aluminum or 316 ss Housing
  • Pipe, Surface, or Manifold Mounting
  • Remote Configuration with HART Communication Protocol in a Single Loop or Multidrop Mode
  • User-Entered Cutoff Point from 0 to 20% of Maximum Flow

View our selection of these items below.


Have a quote from somewhere else? Click Here




Contact Us
Share:



IDP10-T22C01F Configuration:
• Electronics Versions and Output Signal: Intelligent; Digital, HART and 4 to 20 mA (Version -T)
• Structure Code: Transmitter with Traditional Structure - Cover 316 ss, Sensor 316L ss, Fill Fluid Silicone
• Span Limits (Differential Pressure Units): kPa 7 and 210, inH2O 28 and 840, mbar 70 and 2100
• Process Connector Type (Material Same As Process Cover Material): No connectors; both covers tapped for 1/4 NPT (316 ss only, no side vents)
• Conduit Connection and Housing Material: 1/2 NPT Conduit Connection, Aluminum Housing
• Electrical Safety: FM Approved, Division 1 Intrinsically Safe, Explosion Proof, Dust-Ignition Proof; and Non-Incendive, Division 2, Classes I, II, and III. Zone approved intrinsically safe AEx ia IIC.

Part Number: NC52K0226B



Stock # 84263-1




IDP10-T22C21F-M1L1 Configuration:
• Electronics Versions and Output Signal: Intelligent; Digital, HART and 4 to 20 mA (Version -T)
• Structure Code: Transmitter with Traditional Structure - Cover 316 ss, Sensor 316L ss, Fill Fluid Silicone
• Span Limits (Differential Pressure Units): kPa 7 and 210, inH2O 28 and 840, mbar 70 and 2100
• Process Connector Type (Material Same As Process Cover Material): 1/2 NPT, Not with Structure Codes 78 or 79, or Pressure Seals
• Conduit Connection and Housing Material: 1/2 NPT Conduit Connection, Aluminum Housing
• Electrical Safety: FM Approved, Division 1 Intrinsically Safe, Explosion Proof, Dust-Ignition Proof; and Non-Incendive, Division 2, Classes I, II, and III. Zone approved intrinsically safe AEx ia IIC.
• Mounting Bracket Set: Standard Style Painted Steel Bracket with Plated Steel Bolts
• Digital Indicator with Pushbuttons: Digital Indicator, Pushbuttons, and Window Cover

Part Number: NC40F0325B



Stock # 83873-2



  • Description
  • Tech Specs
  • Datasheets / Manuals 
Contact Us
Share:

Description

The Schneider Electric/Invensys/Foxboro I/A Series Model IDP10 is an intelligent, 2-way d/p Cell transmitter that provides precise, reliable measurement of differential pressure. It also transmits a 4 to 20 mA output signal with a superimposed HART digital signal remote configuration and monitoring.
Version -T allows direct analog connection to common receivers while still providing full Digital Communications using a HART Communicator, PC-based configurator or optional LCD Indicator.

Some features include:
- Transmitter available with traditional or low profile structures.
- Aluminum housing has durable, corrosion-resistant epoxy finish; 316 ss housing also available; both meet NEMA 4X and IP66 ratings.
- SIL2-Certified Transmitter offered as an option.
- Optional mounting bracket sets allow pipe, surface, or manifold mounting of transmitter.
- User-entered cutoff point from 0 to 20% of maximum flow.


Product Family: I/A Series, Model IDP10, IDP10, IDP1O, Model IDP10-T, IDP10-T, IDP1O-T
Contact Us
Share:

Specifications