Honeywell TPS Process Manager I/O

Features

  • Process Manager (PM), Advanced Process Manager (APM) and High Performance Process Manager (HPM)
  • Common Set of IOPs and FTAs
  • All IOPs and FTAs are Usable by All (3) Controllers

View our selection of these items below.


Have a quote from somewhere else? Click Here




Contact Us
Share:



Configuration:
• FTA Models: MU-TAOX02, MU-TAOX12, MU-TAOX52, MU-GAOX02, MU-GAOX72, MU-GAOX12, MU-GAOX82
• Output Type: 4-20 mA
• Output Channels: 8
• Output Ripple: 100 mV Peak-to-Peak at Power Line Frequency, Across 250 Load
• Output Temperature Stability: 0.02% Full Scale/C
• Maximum Current Output: 26 mA

Part Number: 51309152-175, 5140492-400, BN11W02-K0408



Stock # 98291-1



  • Description
  • Tech Specs
  • Datasheets / Manuals 
Contact Us
Share:

Description

The Honeywell TPS Process Manager I/O is made up of of Honeywell's Process Manager (PM), Advanced Process Manager (APM) and High Performance Process Manager (HPM) system control and data acquisition devices for industrial process applications. They represent a powerful combination of cost-effective Honeywell controllers which can be applied to solve a broad range of industrial process control problems. The PM, APM, HPM, and EHPM offer highly flexible I/O (input/output) functions for both data monitoring and control. One of the unique features of this family of controllers is its common set of Input/Output Processors (IOPs) and Field Termination Assemblies (FTAs). All IOPs and FTAs are usable by all three controllers (with only minor exceptions).

I/O Processors, along with Field Termination Assemblies (FTAs), perform input and output scanning and processing on all field PM/APM/HPM/EHPM I/O. A redundant I/O Link is standard for maximum security. Optionally, High Level Analog Input, Smart Transmitter Interface, Analog Output, Digital Input and Digital Output processors can be redundant. I/O processing is performed separately from control processing functions so that I/O scan rates are completely independent of I/O quantity, controller loading, processing, and alarming. This partitioning of functions allows more efficient use of advanced Control Processor capability and provides for future I/O expansion.

Product Family: MC-PAOX03, MC-PAIH03, MC-PSTX03, MC-PSDX02, MC-PSIM11, MC-PAIL02, MC-PLAM02, MC-PRHM01, MC-PPIX02, MC-PAOX03, MC-PAOY22, MC-PDIX02, MC-PDIS12, MC-PDIY22, MC-PDOX02, MU-PDOY22, MC-PDOY22, MU-PFPX01, MU-IOLM02, MC-IOLM02, MU-IOLX02, MC-IOLX02, MU-ILDX03, MC-ILDX03, MU-ILES01, MU-PSTX03, MU-PSDX02, MU-PSIM11, MU-PAIL02, MU-PLAM02, MU-PRHM01, MU-PPIX02, MU-PDIX02, MU-PDIS12, MU-PDIY22, MU-PDOX02, MU-PDOY22, MU-TAIH02, TAIH12, TAIH22, TAIH52, TAIH62, TSTX03, TSTX13, TSTX53, MU-TAIH12, TAIH52, TSTX13, TSTX53, MU-TSDM02, TSDT02, TSDU02, MU-TAOY22, TAOY52, THAO11, GHAO11, MU-PDIX02, MU-PDIS12, MU-PDIY22, MU-TDOD13, MU-TDOA13, MU-TDOA53, MU-TDOD23, MU-TDOD63, MU-TDON12, MU-TDON52, MU-TDOR12, MU-TDOR52, MU-TDOR22, MU-TDOR62, MU-TDOY22, MU-TDOY62, MU-TDOY23, MU-TDOY63