Configuration:
• Input Range: 4-20mA or 1-5VDC
• Resolution: 1 of 999 counts
• Resolution, Current Mode: 16µA per count
• Resolution, Voltage Mode: 4mV per count
• Accuracy: ±0.1%/1 count @ 25°C; ±0.3%/3 counts @ 0-60°C
• Linearity: 0.1% of full scale
• Input Impedance, Current Mode: 250 ohms
• Input Impedance, Voltage Mode: 1 Megaohm, differential; 0.5 megaohm each input to shield
• Input Protection: 240V rms
• Channel Isolation: 20V/-9.5V (with respect to module shield terminal)
• Module Isolation: 1500V rms for one minute
• Common Mode, Rejection: -86 dB @ 50/60 Hz
• Common Mode, Input Filter: -3 dB down @ 18 Hz; rolloff 20 dB per decade
Part Number: B375-001
Gould / Modicon B351 Datasheet (pdf)